Our Standards

Communication Protocol

Supported protocols:

  1. IEC 60870-5-101
  2. IEC 60870-5-103
  3. IEC 60870-5-104
  4. Distributed Network Protocol, DNP3
  5. Westing House, WISP+
  6. Harris H6000
  7. Modbus RTU
  8. ABB RP570/571
  9. TLC-11M
  10. SEL Relay
  11. OLE Process Control, OPC

We also provide protocol customization, depending on user's requirement.

 

Type Tested Standards

All our products hardware are type tested according to the following standards:

  1. Electrical and Electronic
  2. Electromagnetic
  3. Mechanical and Environment

 

The tests conducted are:

12.00 Normal 0 false false false EN-US X-NONE X-NONE MicrosoftInternetExplorer4

1. Electrical and Electronic Test Report

IEC 60255-5: 2000

Entitled “Electrical Relays - Part 5: Insulation coordination for measuring relays and protection equipment - Requirements and tests.”

MS IEC 60950-1: 2003

Entitled “Information Technology Equipment – Safety- Part 1: General Requirements”.

2. Electromagnetic Test Report

IEC 1000-4-2: 2001

Entitled “Part 4: Testing and measurement techniques. Section 2: Electrostatic Discharge Immunity Test

IEC 1000-4-3: 2002

Entitled “Radiated radio-frequency electromagnetic filed immunity test”.

IEC 1000-4-4: 2004

Entitled “Part 4: Testing and measurement techniques. Section 4: Electrical Fast Transient/Burst Immunity Test”.

IEC 1000-4-5: 2001

Entitled “Part 4: Testing and measurement techniques. Section 5: Surge Immunity Test”.

IEC 1000-4-6: 2001

Entitled “Part 4: Testing and measurement techniques. Section 6: Immunity to conducted disturbance, induced by radio-frequency fields”.

IEC 1000-4-12: 2001

Entitled Part 4: Testing and measurement techniques. Section 12: Oscillatory wave’s immunity test”.

IEC 1000-4-29: 2000

Entitled Part 4: Testing and measurement techniques. Section 29: Voltage dips & short interruptions on dc input power port immunity test”.

EN55022: 2005 Class A (CISPR 22 Class A: 1995)

Entitled “Limits and methods of measurement of radio disturbance characteristics of information technology equipment”.

DD ENV 50204:1996

Entitled “Radiated radio-frequency electromagnetic field – Pulse modulated”.

IEC 60255-5

Entitled “Part 5: Requirements and Test” Clause 6.1.3

IEC 255-22-1: 2000

Entitled “Part 1:1 MHz burst disturbance tests”

IEC 1000-4-8: 2001

Entitled: Part 4: Testing and measurement techniques. Section 8: Power frequency magnetic field immunity test”.

IEC 1000-4-17: 2002

Entitled “Part 4: Testing and measurement techniques. Section 17: Ripple on DC input power port immunity test”

IEC 1000-4-16: 2002

Entitled “Part 4: Testing and measurement techniques. Section 16: Immunity to conducted, common mode disturbance in the frequency range 0Hz to 150kHZ”

3. Mechanical and Environment Test Report

IEC 255-21-1: 1998

Vibration respond test.

Response Test Class 1 Test FC.

Endurance Test: Class sinusoidal, 10 to 150Hz, 1g, 1 octave/min, 1 cycle in 3 orthogonal axes.

IEC 60068-2-30: 1980

Damp Heat Cyclic -12 +12 hours cycles between 25 to 55ºC at 95% RH, 6 cycles.

IEC 60068-2-3: 1985

Damp Heat Steady state- Severity Class 40ºC, 95%, 10 days.

IEC 60068-2-2: 1974

Dry Heat Severity Class 55ºC, 96 hours Test Bb/d

IEC 255-21-2: 1998

Shock Response Test. Peak Acceleration 5gn, Duration of Pulse 30ms, No of pulses: 3 for each direction.

IEC 255-21-2: 1998

Shock Withstand Test. Peak Acceleration 15gn, Duration of Pulse 11ms, No of pulses: 3 for each direction.

 

 


 

 